Permit Number: T19CM05054
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM05054
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2019 PAUL CAMARENA ZONING REVIEW Approved
08/22/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Verify that the AIC rating of the PV disconnect switch 'ACDS-01' is rated for the available fault current per NEC 705.16, 705.22(4).
2. Verify that the location of the PV disconnect 'ACDS-01' is in compliance with 705.31.
3. Verify that there are indeed existing lugs on the bus as stated, to be utilized at the point of the supply side interconnection. Otherwise, provide for a NRTL field evaluation to be performed and approved to maintain the listing of the equipment. NEC 110.3.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.
09/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2019 AMARTIN1 OUT TO CUSTOMER Completed