Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/14/2019 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
08/22/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Verify that the AIC rating of the PV disconnect switch 'ACDS-01' is rated for the available fault current per NEC 705.16, 705.22(4). 2. Verify that the location of the PV disconnect 'ACDS-01' is in compliance with 705.31. 3. Verify that there are indeed existing lugs on the bus as stated, to be utilized at the point of the supply side interconnection. Otherwise, provide for a NRTL field evaluation to be performed and approved to maintain the listing of the equipment. NEC 110.3. Ref; 2018 IBC sec 107.2.1, 2017 NEC. |
09/04/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/10/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |