Review Details: WALK THRU - COMM

Permit Number - T19CM05053
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E03.04. Clarify note #3 indicated at the receptacle in detail for zone 4.
2. Ref; Plan Sheet E00.02. Revise general note #1A to specify the current 2017 NEC. There is no Arizona code.
Ref; 2018 IBC sec107.2.1, 2017 NEC