Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM05050
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/24/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The new electrical load required for the addition is significant enough to require load calcs to insure not overloading the existing 200 amp panel. Provide electrical load calcs . The note at the bottom of the panel schedule states, "REFER TO WRITTEN OUT LOAD CALCULATIONS". Could not locate these calcs on the plans. 2. The branch circuiting shown for the mechanical equipment and outlets do not correlate with the panel schedule. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |