Permit Number: T19CM05050
Parcel: 133383820

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05050
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/18/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. To ensure the existing 200 amp panel is not overloaded, please provide a complete panel schedule including load calcs as stated on the panel schedule. Please fill in the panel directory.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2019 PMARTIN1 OUT TO CUSTOMER Completed