Review Details: COMMERCIAL - TI

Permit Number - T19CM04986
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/26/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide energy efficiency calculations for the building enveloope, mechanical systems, and the interior lighting. Reference: 2018 IECC.
07/26/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Utilize the current 2018 IECC for lighting.
2. Revise the outdoor lighting calcs to reflect the correct installed as well as the existing lumens. Also provide a complete luminaire schedule interior and exterior lighting, include light source color temperature.
Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County Outdoor Lighting Code.
07/26/2019 RMCCOY1 FIRE REVIEW Needs Review
07/26/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change
07/26/2019 ROBERT SHERRY WATER REVIEW Completed
07/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Correct the location of the natural gas shut off valve in detail 101.
08/12/2019 AMARTIN1 ENGINEERING REVIEW Needs Review
08/12/2019 AMARTIN1 ZONING REVIEW Needs Review