Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM04869
Parcel: 12101103E

Address:
6274 E GRANT RD

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T19CM04869
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2019 SMEGGIS1 ZONING REVIEW Approved
07/24/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/24/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/24/2019 MARTIN BROWN FIRE REVIEW Approved
07/24/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/24/2019 SMEGGIS1 ENGINEERING REVIEW Passed
07/24/2019 ROBERT SHERRY WATER REVIEW Completed
07/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. Previous Comment 1: The Plumbing Code was not revised to the 2018 IPC.
2. Previous Comment 2: The water closet calculation should be reviewed. If there are 40 males and 40 females, it would require two water closets for each sex per the IBC Table 2902.1. Section 2902.2 (Exception 2) is not applicable.
3. Previous Comment 4: Please provide written responses to all review comments.