Permit Number: T19CM04869
Parcel: 12101103E

Address:
6274 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04869
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/10/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise to comply with current codes.
07/10/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. The City of Tucson has adopted the 2018 International Codes and the 2017 NEC , correct plans . IBC 107.2.12.
2. Registrant stamps on plans are out dated . Submit plan with proper stamps. IBC 107.2.1.
07/10/2019 ROBERT SHERRY WATER REVIEW Completed
07/10/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. Sheet T1.1; Code Analysis: Please revise all codes to the 2018 I Codes, the 2017 NEC, and verify the requirements for those codes are met.
2. Sheet T1.1; Code Analysis: The plumbing calculations should be revised. The required waterclosets indicate 2. Per Table 2902.1, with 40 males and 40 females, 2 waterclosets would be required for each sex. Please revise.
3. General: Since the architect of record was not involved in changes made to his stamped drawings, he must be contacted to update his seal and review all changes made.
4. General: Please provide written responses to all review comments.
07/10/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise to comply with current codes.
07/24/2019 PMARTIN1 ENGINEERING REVIEW Needs Review
07/24/2019 PMARTIN1 ZONING REVIEW Needs Review
07/24/2019 PMARTIN1 FIRE REVIEW Needs Review