Permit Number: T19CM04832
Parcel: 13336008R

Address:
700 N BONANZA AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T19CM04832
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Completed .
07/08/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the chillers comply with the EER standards of the 2018 IECC.
2. Provide detail showing installation of the backflow preventer.