Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM04659
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2019 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Passed | |
06/28/2019 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/28/2019 | AHINES2 | ENGINEERING | REVIEW | Passed | |
06/28/2019 | JPEELDA1 | FIRE | REVIEW | Approved | |
06/28/2019 | ALEXANDRA HINES | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/28/2019 | PMARTIN1 | OUT TO CUSTOMER | Completed |