Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM04563
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 1; Sheet A000 (Code Analysis); Sheet A-101 (Exiting/Occupancy Plan): The Code Analysis indicates 19 total occupants, while the exit doors indicate 14 total occupants (7 at each exit). Please verify.
2. Previous Comment 2; Sheet A-101; Exiting/Occupancy Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along the unobstructed path of horizontal and vertical egress travel. Part of the exit access travel distance in the Open Office Area is measured along a diagonal line. Please revise.
3. Previous Comment 3; Sheet A-101; Exiting/Occupancy Plan: Per the IBC Table 2902.1, two restrooms would be required for the 19 occupants in a B Occupancy Classification, along with a drinking fountain and a service sink. If this tenant space had a B Occupancy Classification for the previous use, the existing plumbing fixtures would be acceptable. A change in the Occupancy Classification would require a new analysis for all required plumbing fixtures. Please verify.
4. Previous Comment 4; Sheet A-201; Elevation 6: It appears the Sections 4/A-201 and 7/A-201 should be reversed. Please verify.
5. Previous Comment 5; Sheet A-201; Detail 8: Please indicate a reference to this detail on the plans, notes, sections, details, etc.
6. Previous Comment 6; General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
12/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/04/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved