Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM04563
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/22/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 1; Sheet A000 (Code Analysis); Sheet A-101 (Exiting/Occupancy Plan): The Code Analysis indicates 19 total occupants, while the exit doors indicate 14 total occupants (7 at each exit). Please verify. 2. Previous Comment 2; Sheet A-101; Exiting/Occupancy Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along the unobstructed path of horizontal and vertical egress travel. Part of the exit access travel distance in the Open Office Area is measured along a diagonal line. Please revise. 3. Previous Comment 3; Sheet A-101; Exiting/Occupancy Plan: Per the IBC Table 2902.1, two restrooms would be required for the 19 occupants in a B Occupancy Classification, along with a drinking fountain and a service sink. If this tenant space had a B Occupancy Classification for the previous use, the existing plumbing fixtures would be acceptable. A change in the Occupancy Classification would require a new analysis for all required plumbing fixtures. Please verify. 4. Previous Comment 4; Sheet A-201; Elevation 6: It appears the Sections 4/A-201 and 7/A-201 should be reversed. Please verify. 5. Previous Comment 5; Sheet A-201; Detail 8: Please indicate a reference to this detail on the plans, notes, sections, details, etc. 6. Previous Comment 6; General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
12/04/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/04/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
12/06/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |