Permit Number: T19CM04556
Parcel: 132130750

Address:
3300 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM04556
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2019 MARTIN BROWN FIRE REVIEW Approved
08/22/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/22/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Include the results of the gutter calculations on the drawings. Sheet A4.1 calls out a 6" steel tube gutter with no slope given but the calculations show a 6" x 7" gutter at 1/4" per 12" slope. [Initial comment: Provide calculations to demonstrate that the gutter and downspout dimensions comply with the requirements of Section 1106, IPC 2018.]
08/23/2019 LOREN MAKUS ENGINEERING REVIEW Approved
08/23/2019 SAMUEL ROGERS ZONING REVIEW Approved