Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM04556
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please clearly indicate on plans where panic hardware will be provided. |
| 07/08/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T19CM04556 1. Sheet A0.0; Index to Drawings: The sheet with the Roof Plan indicates A2.4 in the index. Please revise. 2. Sheet A0.2; Project Description: This section indicates this is a 'Shell Only' project for the building skin and exterior. This sheet indicates defined interior spaces, occupant loads, and means of egress for two floors. Please revise the Project Description as required. 3. Sheet A0.2; Governing Regulations: Please add the 2009 ICC/ANSI A117.1 accessibility code to this list. 4. Sheet A0.2; Code Narrative (Chapter 5): The allowable building height per the IBC Table 504.3 is 75 feet. Please revise the Narrative and reference that IBC table. 5. Sheet A0.2; Code Narrative (Chapter 5): The allowable number of building stories per the IBC Table 504.4 is three. Please reference that IBC table. 6. Sheet A0.2; Code Narrative (Chapter 5): Please reference the IBC Table 506.2 for the allowable building area. 7. Sheet A0.2; Code Narrative (Chapter 10): The exit access travel distance references the IBC Table 1016.2. Please revise to the 2018 IBC Table 1017.2. 8. Sheet A0.2; Code Narrative (Chapter 10): The dead end corridor maximum length references the IBC Section 1018.4. Please revise to the 2018 IBC Section 1020.4 (Exception 2). 9. Sheet A0.2; Code Plans: On the first and second floor plans, please indicate the various exit travel distances, including travel distance down the stairs per the IBC Section 1017.3.1. 10. Sheet A2.0; Floor Plan Notes: In Note A, please reference the sheet with the Door Schedule. 11. Sheet A2.0; Wall Types: Wall Type M was not located on the plan. Please verify. 12. Sheet A2.0; First Floor Plan: Please add a note to this sheet to reference all sheets with the aluminum storefront elevations. 13. Sheets A2.0 and A2.1; Floor Plans: Please indicate at one location along the wall on Grid Line B,5 the wall type. 14. Sheet A2.0; First Floor Plan: Please indicate at one location along the wall(s) on Grid Line K the wall type(s). 15. Sheet A2.0; First Floor Plan: On Grid Line M between Grid Lines 3 and 3.5, please add Keynote 1 to the plan. 16. Sheet A2.0; First Floor Plan: Please indicate at one location along the wall on Grid Line 1 the wall type. 17. Sheets A2.0 and A2.1; Floor Plans: Building sections 1/A4.0 and 2/A4.0 are not indicated on the plans. Please verify. 18. Sheets A2.0 and A2.1; Floor Plans: Wall section 1/A4.1 is not indicated on the plans. Please verify. 19. Sheet A2.0; First Floor Plan: Please indicate the enlarged plan 1/A4.2 at the Stair 1/Elevator area. 20. Sheet A2.0; First Floor Plan: Please indicate the enlarged plan 2/A4.2 at the Stair 2 area. 21. Sheet A2.1; Second Floor Plan: Please add the Floor Plan Notes A. from Sheet A2.0 to this sheet (Door Schedule). 22. Sheet A2.1: Please add to this sheet to reference Sheet A2.0 for the Wall Schedule. 23. Sheet A2.1; Second Floor Plan: On Grid Line K, at Grid Lines2 and 6, a Keynote designation is incomplete. Please revise. 24. Sheet A2.1 (Second Floor Plan); Sheet A3.0 (South Elevation): AL13 is indicated on the floor plan, but not indicated on the building elevation. Please verify. 25. Sheet A2.2; Roof Types: Roof Type R3 was not located on the plan. Please verify. 26. Sheet A3.0; North Elevation: AL06 is not indicated on the first floor of the elevation. Please provide. 27. Sheets A7.0 and A8.3: Please verify all details on these sheets are referenced on plans, in notes, or on details/sections. 28. General: This review included some issues that are outside the scope of the Project Description on Sheet A0.2. Please respond whether the City of Tucson comments will be addressed on this activity number or on the interior build-out permit at a later date. 29. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 07/09/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The civil utilities plan (sheet 7 of 8) cannot be "for reference only" as it is the only drawing that can be used to construct the building sewer and the domestic water service to the building. 2. Coordinate the FFE for the building with the architect; your elevation is ten feet below that shown by the architect. The backwater valve is still required but check the inverts for the grease interceptor and the termination of the building drain. 3. Verify that the future connections of the vertical stacks comply with the requirements of Section 704.3, IPC 2018 (i.e. the horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks - see the 2" vertical stack near D-3.5). 4. Provide calculations to demonstrate that the gutter and downspout dimensions comply with the requirements of Section 1106, IPC 2018. |
| 07/09/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/09/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/18/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/26/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T19CM04556 - Civic Use Educational - JTED School Building Plan Review (1st Review) for Shell only 3300 S. Park Avenue - PAD 15 Zoning - Related to DP19-0093 TRANSMITTAL DATE: July 26, 2019 DUE DATE: July 29, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has done a review of the building plans and a comparison to the approved Development package DP19-0093 but cannot approve them at this time until all the PDSD Commercial plans reviewers have also approved the building plans and the following zoning comment(s) are addressed. While comparing the building plan set site plan with the site plan in the approved development package, it was noticed that the site plans do not match. The development package site plan will have to be revised to match the site design in the building plan. Contact Steve Shields for further information on revising the DP plan set. Zoning will review the building plans on the next submittal and do a comparison to the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.). 3. COMMENT: If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans. 4. Zoning cannot approve the building plans until the DP is revised and approved; Contact Steve for options on the building plan approval as it relates to revisions to the DP. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans |
| 07/31/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T19CM04556 1) The site plan shown on sheet A1.0 does not match the site plan provided in Development Package DP19-0093. Examples, The accessible parking spaces, trash enclosure and pedestrian circulation path in the southeast portion. Both plans will need to match John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/22/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |