Permit Number: T19CM04538
Parcel: 116060230

Address:
1622 N ANDROS PL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T19CM04538
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T19CM04538
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1. Include the threshold condition at the vehicle doorway or an exterior hinged door when the garage is used for the accessible route.
2. Show the location of a minimum 22" x 30" attic access. Attic access is required for areas exceeding 30 SQ FT with a minimum of 30" of headroom and located in a hallway or readily accessible space, R807.1.

STRUCTURAL PLANS:

1. Show porch beam sizes with appropriate load carrying capacity, R301.1. Update sheet 6.0.
2. Show braced wall lines with maximum spacing of 60', or provide an engineer's calculation, design and seal. Show interior braced wall panels with foundation anchor bolt connection to bottom plates, R602.10.8.3 and R403.1.6, and roof connections, R602.10.8.2 compliant. Update sheet 3.0.

PLUMBING PLANS:

1. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Include gray drain-line discharge of all second story bathing fixtures through an exterior-wall drop for future gravity distribution. Include an aliened purple colored 2" vertical drop to a cleanout cap 2' above grade. The home owner may perform system alteration for future gray water usage. Add the appropriate detail found at the web site: https://www.tucsonaz.gov/files/pdsd/codes-ordinances/Grey_Water_Options_FINAL_.pdf

ELECTRICAL PLANS:

1. Show a minimum 300 SF solar-ready zone on a roof or framing plan, T103.3. Update sheet 6.1.
2. Specify high-efficacy lamps for at least 90% of all lighting fixtures, N1104.1. Update sheet 7.1.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/02/2019 MARTIN BROWN FIRE REVIEW Reqs Change Due to the distance to the nearest fire hydrant, residential fire sprinklers will be required. Add note to cover sheet indicating fire sprinklers will be installed.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/24/2019 QJONES1 APPROVAL SHELF Completed
07/24/2019 QJONES1 OUT TO CUSTOMER Completed
07/24/2019 QJONES1 REJECT SHELF Completed