Permit Number: T19CM04533
Parcel: 141185820

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04533
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2019 MRESS1 ZONING REVIEW Approved
06/26/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The project narative states that the space is changing from retail to a hair salon. Provide ventilation calculations.
06/26/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
06/26/2019 MRESS1 ENGINEERING REVIEW Passed
06/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/26/2019 ROBERT SHERRY WATER REVIEW Completed
06/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that all proposed plumbing fixtures supplied by the others (e.g. shampoo sinks) are listed by a third-party certification agency. Reference: Section 303.4, IPC 2018.
2. Show that the vertical distance from the shampoo sink outlet to the trap weir does not exceed 24". Reference: Section 1002.1, IPC 2018.
06/26/2019 MARTIN BROWN FIRE REVIEW Approved
06/26/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed