| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2019 | MRESS1 | ZONING | REVIEW | Approved | |
| 06/26/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The project narative states that the space is changing from retail to a hair salon. Provide ventilation calculations. |
| 06/26/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/26/2019 | MRESS1 | ENGINEERING | REVIEW | Passed | |
| 06/26/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/26/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/26/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that all proposed plumbing fixtures supplied by the others (e.g. shampoo sinks) are listed by a third-party certification agency. Reference: Section 303.4, IPC 2018. 2. Show that the vertical distance from the shampoo sink outlet to the trap weir does not exceed 24". Reference: Section 1002.1, IPC 2018. |
| 06/26/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/26/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |