Permit Number: T19CM04510
Parcel: 14118530B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04510
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2019 MRESS1 ZONING REVIEW Approved
06/26/2019 MRESS1 ENGINEERING REVIEW Passed
06/27/2019 MARTIN BROWN FIRE REVIEW Approved
06/28/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Verify that a 120 volt WP/GFI receptacle is installed on the roof for mechanical maintenance. NEC 210.63.
2. Provide a complete panel schedule for panel 'FH2A'.
3. Revise conductor sizes for circuits #6 thru #32 panel 'P4' to comply with NEC 310.15B(16).

Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements.
06/28/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an energy analysis (e.g. COMcheck) of the building addition.
2. Provide a detail showing how the fan-coil supports are connected to the building structure.
06/28/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/28/2019 ROBERT SHERRY WATER REVIEW Completed
07/01/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
07/01/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed