Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM04510
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2019 | MRESS1 | ZONING | REVIEW | Approved | |
| 06/26/2019 | MRESS1 | ENGINEERING | REVIEW | Passed | |
| 06/27/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/28/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Verify that a 120 volt WP/GFI receptacle is installed on the roof for mechanical maintenance. NEC 210.63. 2. Provide a complete panel schedule for panel 'FH2A'. 3. Revise conductor sizes for circuits #6 thru #32 panel 'P4' to comply with NEC 310.15B(16). Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
| 06/28/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an energy analysis (e.g. COMcheck) of the building addition. 2. Provide a detail showing how the fan-coil supports are connected to the building structure. |
| 06/28/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/28/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/01/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/01/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |