Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM04509
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/27/2020 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers - Planner PDSD Zoning Review Section PROJECT: T19CM04509 Surf Thru Express Car Wash (4th Review) 10206 E OLD VAIL RD TRANSMITTAL DATE: 2/27/20 DUE DATE: 3/26/20 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: UDC 7.4.6.E.2 - The parking canopies must be setback from the back of the parking spaces a minimum of 1', or the parking canopies must provide a 15' clearance height over the PAAL. Provide a setback dimension or revised height on the plan set. If a 15' height is pursued the Development Package (DP19-0107) will need to be revised. If you have any questions about this transmittal, contact Samuel Rogers at (520) 837-6932 or at Samuel. Rogers@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
03/03/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Are you content to have the vent for the water closet rising to 24" above the floor or the vent for the floor drain rising 6" above the floor before running horizontally? [Third comment: The vents are still shown running horizontally before they have risen to 6" above the flood rim of the fixture they are venting. [Second comment: Notwithstanding the note on sheet P300, the vents for the water closets and floor drains in the two restrooms do not rise vertically to six inches above the plumbing fixtures they serve prior to running horizontally.] [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. water closets, floor drains). Reference: Section 905.4, IPC 2018.] |
03/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. See the "Governing Codes" section on sheet G000. [Third comment: ASHRAE 90.1-2016 is the applicable energy code, not ASHRAE 90.1-2010. Provide documentation to show that the electrical power and lighting systems show compliance with ASHRAE Standard 90.1-2016. [Second comment: The Building Energy Analysis Report was not included with the submitted documents. Note: if the building envelope, HVAC systems, and Service water systems utilize ASHRAE Standard 90.1-2016 to demonstrate compliance with the energy codes adopted by the City of Tucson, then the electrical power and lighting systems must also show compliance with ASHRAE Standard 90.1-2016.] [Initial comment: Demonstrate energy code compliance for the building envelopes of the car wash and the pay station using calculations based on the current code. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.] 2. Comment not addressed. [Third comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section 6.4.2.1, ASHRAE 90.1-2016. [Second comment: The Building Energy Analysis Report was not included with the submitted documents.] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018.] |