Permit Number: T19CM04509
Parcel: 141186070

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM04509
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2020 JPEELDA1 FIRE REVIEW Approved
02/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The vents are still shown running horizontally before they have risen to 6" above the flood rim of the fixture they are venting. [Second comment: Notwithstanding the note on sheet P300, the vents for the water closets and floor drains in the two restrooms do not rise vertically to six inches above the plumbing fixtures they serve prior to running horizontally.] [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. water closets, floor drains). Reference: Section 905.4, IPC 2018.]
02/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. ASHRAE 90.1-2016 is the applicable energy code, not ASHRAE 90.1-2010. Provide documentation to show that the electrical power and lighting systems show compliance with ASHRAE Standard 90.1-2016. [Second comment: The Building Energy Analysis Report was not included with the submitted documents. Note: if the building envelope, HVAC systems, and Service water systems utilize ASHRAE Standard 90.1-2016 to demonstrate compliance with the energy codes adopted by the City of Tucson, then the electrical power and lighting systems must also show compliance with ASHRAE Standard 90.1-2016.] [Initial comment: Demonstrate energy code compliance for the building envelopes of the car wash and the pay station using calculations based on the current code. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.]
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section 6.4.2.1, ASHRAE 90.1-2016. [Second comment: The Building Energy Analysis Report was not included with the submitted documents.] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018.]
02/18/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
02/24/2020 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T19CM04509 - Surf Thru Car Wash
Building Plan Review (3rd Review)
10206 E Old Vail / C-1 Zoning

TRANSMITTAL DATE: February 24th, 2020

DUE DATE: March 2nd, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the Development Package.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers (Mechanical/Plumbing) and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2020 AMARTIN1 OUT TO CUSTOMER Completed