Permit Number: T19CM04464
Parcel: 115050190

Address:
37 E SAHUARO ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04464
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2019 LMAKUS1 ZONING REVIEW Approved
06/21/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide an exhaust system for the domestic range. Reference: Section 505.6, IMC 2018.
06/21/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/21/2019 LOREN MAKUS ENGINEERING REVIEW Passed
06/21/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Floor Plan: For public toilet facilities, the required lavatory shall be located in the same room as the water closet. Reference: Section 405.3.2, IPC 2018.
2. Sheet A1.0; Code Review: The occupant load indicates 2 occupants for the Warehouse. Please revise.
3. Sheet A1.0; Code Review: The Governing Body is indicated as Pima County. Please revise to the City of Tucson.
4. General: Please provide written responses to all review comments.
06/21/2019 ROBERT SHERRY WATER REVIEW Completed
06/21/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.
06/21/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/24/2019 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/02/2019 AMARTIN1 OUT TO CUSTOMER Completed