Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM04464
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2019 | LMAKUS1 | ZONING | REVIEW | Approved | |
| 06/21/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide an exhaust system for the domestic range. Reference: Section 505.6, IMC 2018. |
| 06/21/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/21/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 06/21/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Floor Plan: For public toilet facilities, the required lavatory shall be located in the same room as the water closet. Reference: Section 405.3.2, IPC 2018. 2. Sheet A1.0; Code Review: The occupant load indicates 2 occupants for the Warehouse. Please revise. 3. Sheet A1.0; Code Review: The Governing Body is indicated as Pima County. Please revise to the City of Tucson. 4. General: Please provide written responses to all review comments. |
| 06/21/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/21/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018. |
| 06/21/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/24/2019 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/02/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |