Permit Number: T19CM04462
Parcel: 13705494G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM04462
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2019 DAVID RIVERA ZONING REVIEW Approved
10/28/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A12 - Accessories Legend - Tag 10 coat hooks - is used for the changing table , please amend .IBC 107.2.1.
2. Provide a completed Special Inspection Form for special inspections required . IBC 107.2.1.
Respond to plan review comments in writting .
10/31/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Four vents are still shown as "flat vents on P-3 and P-7." [Initial comment: fixtures they protect prior to running horizontally (i.e. flatvents are not allowed). Reference: Section 905.4, IPC 2018.]
2. Both AC-1 and AC-2 are scheduled as 180 MBH [Initial comment: Coordinate the natural gas demands shown on the Gas Load Calculation (P-3), the Plumbing Schedule (P-3, P-4, and P-5), the gas isometric diagram (P-7), and the AC Unit Schedule (M-1). Check the addition.]
10/31/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm).
10/31/2019 ROBERT SHERRY WATER REVIEW Completed
11/05/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved