Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/25/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
10/28/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A12 - Accessories Legend - Tag 10 coat hooks - is used for the changing table , please amend .IBC 107.2.1. 2. Provide a completed Special Inspection Form for special inspections required . IBC 107.2.1. Respond to plan review comments in writting . |
10/31/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Four vents are still shown as "flat vents on P-3 and P-7." [Initial comment: fixtures they protect prior to running horizontally (i.e. flatvents are not allowed). Reference: Section 905.4, IPC 2018.] 2. Both AC-1 and AC-2 are scheduled as 180 MBH [Initial comment: Coordinate the natural gas demands shown on the Gas Load Calculation (P-3), the Plumbing Schedule (P-3, P-4, and P-5), the gas isometric diagram (P-7), and the AC Unit Schedule (M-1). Check the addition.] |
10/31/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm). |
10/31/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/05/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |