Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM04462
Parcel: 13705494G

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM04462
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2019 MARTIN BROWN FIRE REVIEW Approved
06/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CS1 - Legal Information / Code Analysis - @ Minimum Plumbing Fixtures states - 1 water closet per 75 females = 1 Req'd / 2 water closets provided . Please clarify. IBC 107.2.1.
2. Sheet A12 - Accessories Legend - Tag 10 coat hooks - is used for the changing table , please amend .IBC 107.2.1.
3. Provide a completed Special Inspection Form for special inspections required . IBC 107.2.1.
Respond to plan review comments in writting .
07/02/2019 ROBERT SHERRY WATER REVIEW Reqs Change 1. Clarify the size of the new water meter; the civil plans show a 2" meter but the plumbing plans show a 1-1/2" water meter.
2. Clarify the purpose of the Watts 009 backflow preventer located after the water filter. If this backflow preventer is to be installed in addition to the reduced pressure backflow preventer located after the water meter, include its pressure drop in the water pressure calculations. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities and in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
07/02/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing (e.g. roof and wall insulation). Reference: Section C303.1, IECC 2018, as amended by the City of Tucson.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018.
3. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.4.2 through C403.4.2.3, IECC 2018.
4. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.
07/02/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the distance to the hot water termination from the hot water source (i.e. the recirculating hot water loop) to the restroom lavatories complies with the requirements of Section C404.5, IECC 2018.
2. Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.
4. Notwithstanding note #3 on sheet P-3, four vents are noted as "flatvents". Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (i.e. flatvents are not allowed). Reference: Section 905.4, IPC 2018.
5. Clarify the connected loads or input ratings for each appliance. Southwest Gas, the local gas utility provides natural gas with an energy content of approximately 1,000 BTU per cubic foot (i.e. 1 Cubic Foot per Hour = 1,000 BTUH). Reference: Section 402.1, IFGC 2018.
6. Coordinate the natural gas demands shown on the Gas Load Calculation (P-3), the Plumbing Schedule (P-3, P-4, and P-5), the gas isometric diagram (P-7), and the AC Unit Schedule (M-1). Check the addition.
7. If the manufacturer does not incorporate a sediment trap within the gas-fired equipment (e.g. the water heater), provide a sediment trap downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2018.
07/15/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E1. Revise the NEC code reference to the current 2017 NEC. Also revise the Com Check for the lighting to the current 2018 IECC.
2. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code, Ord.#10963. See section 104 for plan submittal requirements, www.tucsonaz.gov/pdsd.
Ref; 2018 IBC sec 107.2.1, 2018 IECC, 2017 NEC.
07/22/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM04462 - Food Service Use / El Pollo Loco Restaurant
Building Plan Review (1st Review) Related to DP16-0044 Revised
4755 S. Landing Way - Lot 23

TRANSMITTAL DATE: July 22, 2019

DUE DATE: July 23, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the Shell Building plans for compliance with the approved development package. While the building footprint is consistent with the DP as it relates to the zoning review purview Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage, location, and the building package site plan to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by the PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building Plans - Revised building package site plan

Final Status

Task End Date Reviewer's Name Type of Review Description
10/09/2019 QJONES1 APPROVAL SHELF Completed
10/09/2019 QJONES1 OUT TO CUSTOMER Completed
10/09/2019 QJONES1 REJECT SHELF Completed