Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2019 ELISA HAMBLIN ZONING REVIEW Approved
06/14/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation for the restroom exhaust fans so that they operate on the same schedule as the air supplied to the restrooms.
06/14/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/14/2019 EHAMBLI1 ENGINEERING REVIEW Passed
06/14/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/14/2019 ROBERT SHERRY WATER REVIEW Completed
06/14/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the tempered water supply to the restroom lavatories complies with Section C404.5, IECC 2018.
06/14/2019 MARTIN BROWN FIRE REVIEW Approved
06/14/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed