| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2019 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
| 06/14/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the sequence of operation for the restroom exhaust fans so that they operate on the same schedule as the air supplied to the restrooms. |
| 06/14/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/14/2019 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 06/14/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/14/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/14/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how the tempered water supply to the restroom lavatories complies with Section C404.5, IECC 2018. |
| 06/14/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/14/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |