Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T19CM04238
Review Name: RESUBMITTAL
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | David Rivera T19CM04238 Project: T.I. for 265 E. Missouri Street - MMOCL PDSD Zoning Review Section November 19, 2019 1. The building plans cannot be approved zoning at this time. 2. Once the DP has been reviewed and approved zoning will do a building review and comparison of the proposal against the revised and approved Development Package. |
| 11/25/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 1; Sheet 2; Building Code Data: All codes were not revised as requested. Only the National Electric Code has been revised. |
| 12/16/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Third comment: Comment not addressed.] [Second comment: The detail on sheet 3 does not appear to correspond to the structure of the current building and the roof penetration of the exhaust duct does not appear to apply to the construction of the fan platform on the roof.] [Initial comment: Provide structural details for the construction of the roof platforms for the centrifugal exhaust fan and exhaust duct mounted on the roof. Reference: Section 107.2.1, IBC 2018.] 2. Submit the mechanical drawings for review. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/13/2019 | ANY | REJECT SHELF | RECEIVED |