Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM04238
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/03/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | David Rivera T19CM04238 Project: T.I. for 265 E. Missouri Street - MMOCL PDSD Zoning Review Section October 3, 2019 ***The previous zoning comments dated 09/4/2019 are still applicable. The applicant did not respond to the zoning comments from the last review so it is not clear what the applicant is proposing to do with regards to re-submittal of a revised DP. 1. Zoning cannot approve any further permits for this site until a Revised DP has been submitted for review and approval. 2. Also permit T17CM03360 for the 3 Green houses has expired as of 5/11/19. No inspections were ever completed. 3. Contact Steve Shields for information on what is required due to additions to the site that were not approved on DP16-0204. |
| 10/08/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 10; Sheet 2; Building Code Data: Codes were not revised as requested. 2. Previous Comment 13; Sheet 4; Floor Plan: The elevation indicator at the fume hood (Key Note 2) references 2/4. That reference was not revised. 3. Previous Comment 16; Sheet S1; Structural Notes: Note 1 reference to the current code was not revised. 4. Previous Comment 17; Sheet S1; Structural Notes: Note 9 references the details to determine bolt material. The details still do not provide that information. 5. General: Please provide written responses to all review comments. 6. General: Comments 1 through 4 have been redlined on the permit drawings for clarity. Please revise these issues as required. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 10/18/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Second comment: The detail on sheet 3 does not appear to correspond to the structure of the current building and the roof penetration of the exhaust duct does not appear to apply to the construction of the fan platform on the roof.] [Initial comment: Provide structural details for the construction of the roof platforms for the centrifugal exhaust fan and exhaust duct mounted on the roof. Reference: Section 107.2.1, IBC 2018.] 2. Comment not addressed. [Second comment: Calculations not included with submittal.] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018.] |