Permit Number: T19CM04238
Parcel: 120093130

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04238
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 10; Sheet 2; Building Code Data: Codes were not revised as requested.
2. Previous Comment 13; Sheet 4; Floor Plan: The elevation indicator at the fume hood (Key Note 2) references 2/4. That reference was not revised.
3. Previous Comment 16; Sheet S1; Structural Notes: Note 1 reference to the current code was not revised.
4. Previous Comment 17; Sheet S1; Structural Notes: Note 9 references the details to determine bolt material. The details still do not provide that information.
5. Previous Comment 18; General: The Special Inspection Certificate was not provided.
6. General: Please provide written responses to all review comments.
09/04/2019 DAVID RIVERA ZONING REVIEW Reqs Change David Rivera

PDSD Zoning Review Section
September 4, 2019

Project: T.I. for 265 E. Missouri Street - MMOCL

1. Zoning cannot approve any further permits for this site until a Revised DP has been submitted for review and approval.

2. Also permit T17CM03360 for the 3 Green houses has expired as of 5/11/19. No inspections were ever completed.

3. Contact Steve Shields for information on what is required due to additions to the site that were not approved on DP16-0204.
09/06/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The detail on sheet 3 does not appear to correspond to the structure of the current building and the roof penetration of the exhaust duct does not appear to apply to the construction of the fan platform on the roof. [Initial comment: Provide structural details for the construction of the roof platforms for the centrifugal exhaust fan and exhaust duct mounted on the roof. Reference: Section 107.2.1, IBC 2018.]
2. Receptacle for roof-mounted fan not found on electrical poe=wer plan. [Initial comment: Provide a receptacle outlet near the roof-mounted centrifugal exhaust fan for maintenance purposes. Reference: Section 306.5.2, IMC 2018.
3. Calculations not included with submittal. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018.]
09/06/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/06/2019 ROBERT SHERRY WATER REVIEW Completed
09/12/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved