Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM04238
Parcel: 120093130

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04238
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 1 (Square Footage); Sheet 2 (Site Plan): The Site Plan indicates the "Production Kitchen" area is 2665 SF, while Sheet 1 indicates the total existing building area is 15,000 SF. Please indicate on Sheet 1 the SF and the occupant load for this permit.
2. Sheet 1; Occupants: The occupant load indicated is based on 500 SF/occupant. Per the IBC Table 1004.5, an Agricultural Building should have the occupant load based on 300 SF/occupant. Please clarify.
3. Sheet 1; Allowable Area Increases: The Allowable Area indicates a 100% fire sprinkler increase (17,000 SF), while the IBC Table 506.2 (F-1 with S-1) indicates 34,000 SF. Please revise.
4. Sheet 1; Number of Stories: The Allowable Number of stories indicates 1, while the IBC Table 504.4 indicates two stories are allowed (F-1 and S). Please revise.
5. Sheet 1; Height to Roof Line: The Allowable Height to Roof Line indicates 40', while the IBC Table 504.3 indicates 60' (F with S). Please revise.
6. Sheet 1; Exits: The Corridor Protection indicates a fire rating is not required per 1004.3.2.1. Please revise the Section reference (this is a 2012 IBC reference).
7. Sheet 1; Panic Hardware: Per the IBC Section 1010.1.10, panic hardware is required in Group A or Group E Occupancy Classifications where the occupant load is 50 or greater. This is not pertinent to F-1 Occupancy Classifications. See Section 1010.1.9.4 (2) for locks and latches for this project, and add a note on this sheet.
8. Sheet 1; Codes: Please revise the Accessibility Code to the 2009 ICC/ANSI A117.1.
9. Sheet 1; Plumbing Fixtures: Please indicate on this sheet the total number of occupants (revise as required per Comment 2), and the total number of required plumbing fixtures using the IBC Table 2902.1.
10. Sheet 2; Building Code Data: Please revise all codes as required.
11. Sheet 4; Floor Plan: Key Notes 15 and 24 were not located on the Floor Plan. Please verify.
12. Sheet 4; Floor Plan: In the Prod Kitchen, an elevation indicator at the cabinets (Key Note 16) references 1/4. Please revise that reference.
13. Sheet 4; Floor Plan: In the Analytics Lab, an elevation indicator at the fume hood (Key Note 2) references 2/4. Please revise that reference.
14. Sheet 5; Elevation 1: The 34" dimension should be indicated from the finished floor to the top of the counter. Please revise.
15. Sheet 5; Ceiling Plan: Key Note 4 was not located on the Ceiling Plan. Please verify.
16. Sheet S1; Structural Notes: Note 1 references the 2012 IBC. Please revise that reference.
17. Sheet S1; Structural Notes: Note 9 (bolts) indicates bolts are "ASTM A307 or ASTM A325N- Refer to details". The details do not provide that information. Please verify.18. 18. General: Please provide the Special Inspection Certificate with Parts A and B completed.
19. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
06/28/2019 JPEELDA1 FIRE REVIEW Approved
07/01/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Where is the hot water source located in relation to the installation of the new plumbing? Reference: Section 607.2, IPC 2018.
2. Will any water be distributed to the new flowering room? Reference: Section 107.2.1, IBC 2018.
07/01/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide structural details for the construction of the roof platforms for the centrifugal exhaust fan and exhaust duct mounted on the roof. Reference: Section 107.2.1, IBC 2018.
2. Provide legible manufacturer's equipment data and installation instructions for the new equipment (e.g. extraction booth, rotary evaporator, heating mantle, etc.). Reference: Sections 301 and 304.1, IMC 2018.
3. Provide maintenance access, a service platform, a switched luminaire, and an electrical outlet for each of the two tube axial fans on the extraction booth. Reference: Section 306.3, IMC 2018.
4. Provide a receptacle outlet near the roof-mounted centrifugal exhaust fan for maintenance purposes. Reference: Section 306.5.2, IMC 2018.
5. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018.
6. The extraction booth has a purge mode that exhausts 1500 CFM. Will the controls for fan coil FC-2 accommodate the increased make up air requirement? Reference: Section 501.4, IMC 2018.
7. Provide justification for not providing a hood for the four double-stack convection ovens. Reference: Section 507.1, IMC 2018.
8. Secure the refrigerant circuit access ports of the new condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
07/01/2019 ROBERT SHERRY WATER REVIEW Reqs Change Provide the total demand that the existing water meter will serve after this tenant improvement is complete. Reference: Section 107.2.1, IBC 2018.
07/09/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Cover Sheet.
Revise the NEC reference to 2017. There is no 2018.
2. Ref; Plan Sheet E1.0.
Revise the reference in the electrical specs for the NEC to 2017.
3. Ref; Plan Sheet E5.0.
Indicate what is utilized for the grounding electrode for the new 45 KVA transformer. Also show the size and type of the grounding electrode conductor. NEC 250.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.
07/11/2019 DAVID RIVERA ZONING REVIEW Reqs Change David Rivera

PDSD Zoning Review Section
July 11, 2019

Project: T.I. for 265 E. Missouri Street - MMOCL

1. Zoning cannot approve any further permits for this site until a Revised DP has been submitted for review and approval.

2. Contact Steve Shields for information on what is required due to additions to the site that were not approved on DP16-0204.
07/15/2019 LOREN MAKUS ENGINEERING REVIEW Passed