Permit Number: T19CM04236
Parcel: 13624446A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM04236
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: All structural drawings must be sealed, signed, and dated by the engineer of record. Please provide.
06/21/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T19CM04236

1) Canopy D 5. Show in the 5 Panel Semi Cantilever detail on sheet S.2 the ground clearance from the lowest structural member to finished grade at the point which the canopy crosses into the parking area access lane. Minimum clearance is 15' so as to not impact service vehicle circulation

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
07/10/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/11/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM04236 - Medical Service Outpatient Use approved per DP18-0016
Vehicle Parking Lot Solar Canopies (1st Review) -
6950 E Golf Links Road - O-3, C-1 and C-2 Zoning

TRANSMITTAL DATE: July 11, 2019

DUE DATE: July 12, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has reviewed the building plans for the three sizes of the vehicle parking lot solar canopies for the El Rio Southeast Clinic but cannot approve the plans at this time.


02. COMMENT: While the canopy structures are consistent with the drawings proposed on the revised Development Package (DP) and meet the PAAL setbacks and heights within the PAALs, zoning cannot approve the plans until a DDO or B of A application is processed and approved for the canopy facing Langley Avenue and the DP revisions have been approved by PDSD Review Staff.


03. COMMENT: Zoning will review the building plans on the next submittal to assure compliance with the latest version of the approved DP and DDO or B of A approval.



If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2019 SBORZAK1 APPROVAL SHELF Completed
08/29/2019 SBORZAK1 OUT TO CUSTOMER Completed
08/29/2019 SBORZAK1 REJECT SHELF Completed