Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM04235
Parcel: 12405057A

Address:
915 E 4TH ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T19CM04235
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the ventilation calculations, using a more appropriate description of the 2880 SF area (i.e.. reception area rather than office). Reference: Section 403.3.1.1, IMC 2018.