Permit Number: T19CM04194
Parcel: 13316030E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04194
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2019 STEVE SHIELDS ZONING REVIEW Approved
06/12/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the ventilation calculations, i.e identify the storage rooms, the offices, etc. See Table 403.3.1.1 for the category telephone/data entry.
06/12/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide a fused disconnect to protect the secondary feeders of the 30KVA transformer at the transformer location. NEC art.240.4, 240.21, 450.14.
06/12/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
06/12/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
06/12/2019 ROBERT SHERRY WATER REVIEW Completed
06/12/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/12/2019 MARTIN BROWN FIRE REVIEW Approved
06/12/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed