Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM04194
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2019 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/12/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the ventilation calculations, i.e identify the storage rooms, the offices, etc. See Table 403.3.1.1 for the category telephone/data entry. |
| 06/12/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a fused disconnect to protect the secondary feeders of the 30KVA transformer at the transformer location. NEC art.240.4, 240.21, 450.14. |
| 06/12/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 06/12/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/12/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/12/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/12/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/12/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |