Permit Number: T19CM04125
Parcel: 137055240

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04125
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2019 NICHOLAS ROSS ZONING REVIEW Approved
06/10/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/10/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide compliance with the 2018 IECC for interior lighting.
2. Please provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting.
Ref; 2017 NEC, 2018 IECC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
06/10/2019 NROSS1 ENGINEERING REVIEW Passed
06/10/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet LS1.0 illustrates exiting through stock area ,and through hallway , two intervening spaces , provide code analysis to support this exit through intervening spaces . IBC 1016.2.
Respond to plan review comments in writting .
Cloud revisions on plans .
06/10/2019 ROBERT SHERRY WATER REVIEW Completed
06/10/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/10/2019 JVINCEN1 FIRE REVIEW Reqs Change Second required exit cannot exit through a store/stock room.
06/17/2019 PMARTIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed