Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM04125
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2019 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 06/10/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/10/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with the 2018 IECC for interior lighting. 2. Please provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. Ref; 2017 NEC, 2018 IECC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
| 06/10/2019 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 06/10/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet LS1.0 illustrates exiting through stock area ,and through hallway , two intervening spaces , provide code analysis to support this exit through intervening spaces . IBC 1016.2. Respond to plan review comments in writting . Cloud revisions on plans . |
| 06/10/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/10/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/10/2019 | JVINCEN1 | FIRE | REVIEW | Reqs Change | Second required exit cannot exit through a store/stock room. |
| 06/17/2019 | PMARTIN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |