Permit Number: T19CM04121
Parcel: 119040910

Address:
3630 S CLARK AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM04121
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2019 NICHOLAS ROSS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Nick Ross
Lead Planner

PROJECT:
T19CM04121
3630 S Clark Ave
Carport

TRANSMITTAL: 8/28/19
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a).

The applicant is proposing a carport that will be entered from the side, not reducing the driveway length. The required setback based on an 11'10" height is 20'. The proposed setback is 5'10". Structure meets side yard setbacks. DDO Required.
08/28/2019 NROSS1 ENGINEERING REVIEW Passed
08/28/2019 NROSS1 NPPO REVIEW Passed
10/16/2019 QJONES1 BUILDING-RESIDENTIAL REVIEW Needs Review