Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM04029
Parcel: 117120200

Address:
33 N 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM04029
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2019 JPEELDA1 FIRE REVIEW Reqs Change Code sheet references smoke detectors and fire alarm system? Is the occupancy non-seperated? If it is, the most restrictive would be used and that is the A occupancy. Smoke detectors are required for a R2 but would cause false alarms in an area like this. If still required we would recommend heat detectors. Please clarify
07/10/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1.2 - General Information - states 2,214 total interior square feet , - 2018 IBC Information - states - public 430.84 sq.ft. , and - kitchen 1289.24 sq.ft. the total is 1720.08sq.ft. . 2,214sq.ft. - 1720.08sq.ft. = 493.92sq.ft. , clarify square footages and illustrate on floor plan and necessary documents . IBC 107.2.1.
2. Sheet G1.2 - 2018 IBC Information - states occupancy type B , provide code analysis to support this . IBC 107.2.1.
3. Sheet G1.2 - Provide and illustrate on floor plan the exit access travel distance from the basement storage . IBC 1017.
4. Sheet G1.2 - Exit access travel distance - 300' Maximum ; 100' actual - this applies to multiple exits , this project has one exit , provide correct code analysis . IBC 1017 , IBC Table 1006.2.1.
5. Provide the existing floor plan of tenant space , illustrating all existing components , and provide demo plan if necessary , for clarity . IBC 107.2.1.
6. Sheet G1.2 - Exit Door construction and landing per seperate permit , clarify this statement . IBC 107.2.1.
7. Provide section drawings . IBC 107.2.1
8. Provide a completed Special Inspection Form per structural plans . IBC 107.2.1.
Respond in writting to plan review comments .
Cloud all revisions.
07/15/2019 ROBERT SHERRY WATER REVIEW Completed
07/15/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Termination of the excess pressure relief from the water heater over an elevated service sink is not an approved location. Reference: Section 504.6 (6), IPC 2018.
2. Clarify how the water heater pan drain can terminate over a service sink with a rim that is 15" higher than the pan outlet. Reference: Section 504.7.2, IPC 2018.
3. Coordinate the flowrate of the recirculation pump, RP-1, shown in detail 1/P3 with the plumbing fixture specifications. Reference: Section 107.2.1, IBC 2018.
4. Detail 1/P3 shows the cold water shut off valve located between the cold-water check valve and the expansion tank; is this correct? Reference: Section 107.2.1, IBC 2018.
5. Verify that the distance to the hot water termination from the hot water source complies with the requirements of Section C404.5, IECC 2018.
6. Verify that the vent for the grease interceptor will rise vertically to at least 6" above the flood rim of the interceptor prior to running horizontally. Reference: Section 905.4, IPC 2018.
7. A dishwasher may not discharge through a hydromechanical grease interceptor. Verify how the discharge from the dishwasher can be accommodated by the hydromechanical grease interceptor with the Pima County Regional Wastewater Reclamation Department. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
8. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
9. Verify that the Pima County Regional Wastewater Reclamation Department will allow the indirect drains from the prep sink (K-027), the milk/coffee tower (K-085), and the espresso machine (K-089) to bypass the grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
07/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise detail 1/M4 to indicate the current codes and the display the minimum slope for the grease exhaust duct. Reference: Section 107.2.1, IBC 2018 and Section 506.3.7, IMC 2018.
2. Provide cleanouts for the grease exhaust duct that are no further than 20-feet apart. Reference: Sections 506.3.9, IMC 2018.
3. Section 506.3.11.2, IMC 2018 requires field-applied duct enclosures to continuously enclose the grease exhaust duct from the origin of the grease exhaust duct to the termination of the duct. A protective barrier is required in locations where physical damage of the grease exhaust duct is possible.
4. The grease exhaust fan, EF-1, appears to be within five-feet of the two evaporative coolers especially if the fan inlet duct is drawn 60" long per detail 5/M4. Clarify the scroll orientation and show any extension of the fan outlet needed to obtain an outlet height of 40" above the roof surface. Reference: Sections 506.3.13.1 and 506.3.13.3, IMC 2018.
07/25/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. As requested per the last electrical plan review:
(a) Could not locate a written response for the review comments.
(b) Provide a 120 volt GFI protected maintenance receptacle for the roof top mechanical units as required per NEC 210.68.
(c) Include all the exhaust fans in the mechanical equipment schedule.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.