Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a rooftop maintenance receptacle within 25 feet of EF1 and EC1. NEC 210.68.
2. The roof electrical (E2.1) plan shows 3 EF's. Please include the other 2 EF's on the Mechanical schedule and Panel schedules.
Ref; 2018 IBC 107.2.1, 2017 NEC.