Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM04029
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a rooftop maintenance receptacle within 25 feet of EF1 and EC1. NEC 210.68. 2. The roof electrical (E2.1) plan shows 3 EF's. Please include the other 2 EF's on the Mechanical schedule and Panel schedules. Ref; 2018 IBC 107.2.1, 2017 NEC. |
| 06/11/2019 | ERIC NEWCOMB | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/11/2019 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/11/2019 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 06/11/2019 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 06/11/2019 | ENEWCOM1 | WATER | REVIEW | Needs Review | |
| 06/11/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/11/2019 | ENEWCOM1 | FIRE | REVIEW | Needs Review | |
| 06/11/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |