Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM03980
Parcel: 11611005K

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03980
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a watertight pan of galvanized steel, aluminum, or other approved material under the water heater with a drain to an approved location. Reference: Section 504.7, IPC 2018.
06/24/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a programmable thermostat for each air handler that complies with the requirements of Section R403.1.1 (N1103.1.1), IECC (IRC) 2018.
2. Provide calculations showing mechanical ventilation for the building. Reference: Section R403.6, IECC 2018 and Section 505.3 (exception 1), IMC 2018.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson.
06/24/2019 ROBERT SHERRY WATER REVIEW Completed
07/09/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/10/2019 QJONES1 APPROVAL SHELF Completed
07/10/2019 QJONES1 OUT TO CUSTOMER Completed
07/10/2019 QJONES1 REJECT SHELF Completed