Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM03976
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a watertight pan of galvanized steel, aluminum, or other approved material under the water heater with a drain to an approved location. Reference: Section 504.7, IPC 2018. |
| 06/24/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a programmable thermostat for each air handler that complies with the requirements of Section R403.1.1 (N1103.1.1), IECC (IRC) 2018. 2. Provide calculations showing mechanical ventilation for the building. Reference: Section R403.6, IECC 2018 and Section 505.3 (exception 1), IMC 2018. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson. |
| 06/24/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/09/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/10/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 07/10/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 07/10/2019 | QJONES1 | REJECT SHELF | Completed |