Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM03974
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/11/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/04/2019 | SBORZAK1 | OUT TO CUSTOMER | Completed |