Permit Number: T19CM03963
Parcel: 132164670

Address:
4632 S CALLE JON

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM03963
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2019 TOM WEIDEMAN ZONING REVIEW Passed
06/04/2019 TOM WEIDEMAN ENGINEERING REVIEW Passed
06/06/2019 DMCCART1 BUILDING-RESIDENTIAL REVIEW Reqs Change Existing Eaton 200A. Solar Ready, MPE4040PV200BTS, Electric Panel and Meter; please provide spec sheet pertaining to maximum backfeed breaker

Backfeed beaker of 60 Amp on 200 A bus rating, exceeds 120%. Need 225 bus rating or derate the panel to 175A OR Provide Specsheet for Eaton 200A. Solar Ready, MPE4040PV200BTS, Electric Panel and Meter, that 60 amp back feed is ok.

Email to daniel.mccarthy@tucsonaz.gov

Thank you.