Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T19CM03963
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/04/2019 | TOM WEIDEMAN | ENGINEERING | REVIEW | Passed | |
06/04/2019 | TOM WEIDEMAN | ZONING | REVIEW | Passed | |
06/06/2019 | DMCCART1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Existing Eaton 200A. Solar Ready, MPE4040PV200BTS, Electric Panel and Meter; please provide spec sheet pertaining to maximum backfeed breaker Backfeed beaker of 60 Amp on 200 A bus rating, exceeds 120%. Need 225 bus rating or derate the panel to 175A OR Provide Specsheet for Eaton 200A. Solar Ready, MPE4040PV200BTS, Electric Panel and Meter, that 60 amp back feed is ok. Email to daniel.mccarthy@tucsonaz.gov Thank you. |