Review Details: COMMERCIAL - TI
Permit Number - T19CM03942
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/04/2019 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/04/2019 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/04/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The OCPD/branch circuit conductors for the water heater is undersized. See plumbing schedule for water heater power requirements. 4100 watts/ 208 volts= 19.71 amps x 125% = 24.5 amps. NEC art 422.10A, 422.13. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
06/04/2019 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
06/04/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/04/2019 | RMCCOY1 | WATER | REVIEW | Passed | |
06/04/2019 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/04/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/05/2019 | JPEELDA1 | FIRE | REVIEW | Approved |