Permit Number: T19CM03942
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03942
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2019 STEVE SHIELDS ZONING REVIEW Approved
06/04/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Approved
06/04/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The OCPD/branch circuit conductors for the water heater is undersized. See plumbing schedule for water heater power requirements. 4100 watts/ 208 volts= 19.71 amps x 125% = 24.5 amps. NEC art 422.10A, 422.13.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements.
06/04/2019 SSHIELD1 ENGINEERING REVIEW Passed
06/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/04/2019 RMCCOY1 WATER REVIEW Passed
06/04/2019 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Approved
06/04/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/05/2019 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2019 QJONES1 APPROVAL SHELF Completed
06/17/2019 QJONES1 OUT TO CUSTOMER Completed
06/17/2019 QJONES1 REJECT SHELF Completed