Permit Number: T19CM03917
Parcel: 121070140

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03917
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2019 JPEELDA1 FIRE REVIEW Approved
06/10/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review 1. Sheet A1.0 - Sheet Index - sheets A7.0 and sheet E6.0 are noted but not attached to plans , sheet E1.1 and sheet E4.1 are not noted but are attached to plans . IBC 107.2.1.
2. Sheet A1.0 - Code Analysis Data - illustrate codes referenced in this section. IBC 107.2.1.
3. Sheet A1.0 - Code Analysis Data - 3 Occupancy -- Group ( See Table 5A ) A2 Restaurant See 303.3 ; Table 5A is not in the 2018 IBC ,if that is what you are referencing , provide the correct code analysis and reference ; See 303.3 , clarify this with correct code analysis and code statement . IBC 107.2.1.
4. Sheet A1.0 - Code Analysis Data - Occupancy Per Individual Space - Provide correct code analysis for Occupancy and Occupant Load .IBC 107.2.1.
5. Provide a complete Means of Egress System illustrated on plans .IBC Chap. 10 .
6. Provide all exit width calculations . IBC 1005.
7. Sheet A1.0 - Code Analysis Data - Plumbing Fixtures - provide the minimum number of required plumbing fixtures per IBC Chapter 29 . IBC 107.2.1.
8. Illustrate outside seating area on plans . IBC 107.2.1.
06/13/2019 ROBERT SHERRY WATER REVIEW Completed
06/13/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. All plumbing fixtures being provided by others (e.g. hand sink, 3-compartment sink) shall be third-party listed. Reference: Sections 303.4 and 402, IPC 2018.
2. Clarify how tempered water will be provided for the new public restroom lavatories using the relocated instantaneous water heaters. Reference: Sections 416.5 and 607.1.2, IPC 2018.
06/13/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/01/2019 AVAUGHN1 ELECTRICAL-COMMERCIAL REVIEW Needs Review