Permit Number: T19CM03861
Parcel: 117111060

Address:
117 N 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03861
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/31/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the walk-in cooler meets the energy efficiency requirements of Section C403.10.2, IECC 2018.
05/31/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/31/2019 ROBERT SHERRY WATER REVIEW Reqs Change Clarify the size of the existing water meter: it is noted as both 3/4" and 1".
05/31/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/31/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The required lavatories shall be located within the same room as the required water closets. Reference: section 405.3.2, IPC 2018.
06/03/2019 SSHIELD1 ENGINEERING REVIEW Passed
06/03/2019 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT:
T19CM03861
117 N 6th Ave
TI - Bar

TRANSMITTAL: June 3, 2019
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8) & RNA (UDC 5.12.7).

This site is located in the down town and RNA. Due to removal of exterior window Historic and RNA review is required.
06/03/2019 MARTIN BROWN FIRE REVIEW Approved