Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM03823
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/17/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the termination of the condensate drains for the rooftop units: the roof drains terminate in an area that is not capable of absorbing the condensate without surface drainage. Reference: Section 302.2.1 (3), IMC 2018 as amended by the City of Tucson. [Initial comment: Condensate drains shall be terminated at an approved disposal location (i.e. a splash block on the roof is not an approved termination. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.] 2. Verify the scheduled capacity of RTU-9 (60.9 MBH Total/48.9 MBH Sensible); the load calculations show 37.8 MBH Total/35.1 MBH Sensible. Other than in the load calculations, where does RTU-20 occur? [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.] |
| 06/18/2019 | STEVE SHIELDS | ZONING | REVIEW | Approv-Cond | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: At Home - TI with Accessible parking upgrade. T19CM03823 Building Plan (2nd Review) TRANSMITTAL DATE: June 18, 2019 1. The building plans have been reviewed by Zoning Review Section and acknowledge that all Zoning comments have been addressed. Zoning has conditionally approved the building plan but will not stamp the plans until approved by Mechanical review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/19/2019 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 06/19/2019 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 06/19/2019 | TWEIDEM1 | REJECT SHELF | Completed |