Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM03823
Parcel: 12701008A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03823
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2019 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: at home - TI with Accessible parking upgrade.
T19CM03823
Building Plan (1st Review)

TRANSMITTAL DATE: May 31, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The vehicle parking calculation is not correct. Per Unified Development Code (UDC) Table 7.4.4-1, RETAIL TRADE USE GROUP, the required number of vehicle parking spaces is based on a ratio of 1 space per 300 sq. ft. gross floor area or a total of 333 spaces required.

3. The "ADA Accessible Spaces Porvided" number does not match what is shown on the plan and should be 10.

4. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/03/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
06/04/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Identify what appears to be a supply diffuser in the count room labeled "F 200 8" ?"; provide balancing data for the diffuser in the count vestibule. Reference: Section 107.2.1, IBC 2018.
2. Condensate drains shall be terminated at an approved disposal location (i.e. a splash block on the roof is not an approved termination. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
3. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
06/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the distance to the hot water termination (e.g. lavatory faucets in a public restroom) from the hot water source complies with the requirements of Section C404.5, IECC 2018.
2. Provide structural calculations for the mounting shelf for the water heater to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018.
3. Keynote 4 on sheet P3.0 calls for a ¾" hot water drop to the two LAV-1 units from a ½' hot water supply pipe. Is this intended?
4. Keynote 9 on sheet P3.0 calls for a 4" sanitary waste down from a water closet but the 4" then connects to a 3" horizontal drain. Reference: Sections 704.2 and 708.1.5, IPC 2018.
5. The entry canopy does not have a means of secondary roof drainage. Provide structural calculations to show that the canopy can safely support the maximum possible water depth caused by ponding if the primary roof drains are assumed to be blocked. Reference: Section 1101.7, IPC 2018.
06/04/2019 MARTIN BROWN FIRE REVIEW Approved
06/04/2019 ROBERT SHERRY WATER REVIEW Completed
06/07/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved