Permit Number: T19CM03823
Parcel: 12701008A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03823
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/30/2019 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Needs Review
05/30/2019 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/30/2019 ENEWCOM1 FIRE REVIEW Needs Review
05/30/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
05/30/2019 ENEWCOM1 WATER REVIEW Needs Review
05/30/2019 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Needs Review
05/31/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
05/31/2019 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: at home - TI with Accessible parking upgrade.
T19CM03823
Building Plan (1st Review)

TRANSMITTAL DATE: May 31, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The vehicle parking calculation is not correct. Per Unified Development Code (UDC) Table 7.4.4-1, RETAIL TRADE USE GROUP, the required number of vehicle parking spaces is based on a ratio of 1 space per 300 sq. ft. gross floor area or a total of 333 spaces required.

3. The "ADA Accessible Spaces Porvided" number does not match what is shown on the plan and should be 10.

4. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2019 TWEIDEM1 APPROVAL SHELF Completed
05/31/2019 TWEIDEM1 OUT TO CUSTOMER Completed
05/31/2019 TWEIDEM1 REJECT SHELF Completed