Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM03761
Parcel: 11446027E

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T19CM03761
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1 - Project Code Review - Occupant Loads : 4. Fitness Center notes an occupant load factor of 100 . IBC Table 1004.5 states the occupant load factor as 15 net . Calculate occupant loads with correct information . IBC 107.2.1, IBC Table 1004.5.
2. Sheet TS1 - Project Code Review - Occupant Loads : 1. Office and 2. Business Center notes an occupant load factor of 100 . IBC Table 1004.5 states the occupant load factor as 150 gross . Calculate occupant loads with correct information . IBC 107.2.1 , IBC Table 1004.5.
3. Sheet TS1 - Project Code Review - Occupant Loads 5. Storage 387/300 = 1 occupant . IBC 311.1.1 Accessory Storage Spaces . A room or space used for storage purposes that is accessory to another occupancy shall be classified as part of that occupancy . Calculate occupant loads with correct information .IBC 107.2.1 , IBC 311.1.1.
4. Sheet TS1 - provide code analysis for mininum number of required plumbing fixtures . IBC 2902 , IBC 107.2.1.
5. Sheet EP1.0 - Means of Egress Width Calculations ; recalculate using correct occupant loads . IBC 107.2.1.
6. Sheet EP1.0 - Means of Egress Width Calculations ; second note references IBC section 1008.1.8.3 ; 1008.1.8.3 is not in the IBC , supply correct code reference . IBC 107.2.1
7. Sheet A1.0 - 2nd Floor Plan - references Detail 2 on sheet A4.0 , but detail 2 is not on sheet A4.0 . IBC 107.2.1.
8. Sheet S1.0 - Footing (F) Schedule - notes F-5 and F-6 footings , but F-5 and F-6 are not located in the Structural Calculations . IBC 107.2.1.
9. Sheet S1.0 - Beam (B) Schedule - notes B-6 and B-7 beams , but are not located in the Structural Calculations . IBC 107.2.1.
10. Sheet S1.0 - Column (C) Schedule - notes P-1 and P-2 columns , but are not located in the Structural Calculations . IBC 107.2.1.
- Respond to plan review comments in writting .
- Cloud revisions on plans .
06/03/2019 MARTIN BROWN FIRE REVIEW Approved
06/10/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the required minimum plumbing fixtures for the building. Reference: Section 2902.1, IBC 2018.
06/10/2019 ROBERT SHERRY WATER REVIEW Completed
06/11/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018.
06/21/2019 LOREN MAKUS ENGINEERING REVIEW Passed
06/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/02/2019 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2019 ANY REJECT SHELF RECEIVED